LC1D25F7  Power Contactor is a  TeSys D contactor, 3 poles (3NO), for motor control applications up to 25A/690V AC-3/3e (11kW@400V).

It provides a 110V 50/60Hz AC coil, 1NO+1NC built-in auxiliary contacts (NC mirror certified), connection by screw clamp terminals.

For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (45mm width), DIN-rail mounting or screw fixing. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).

 

 

 

Main
range

TeSys

 
product name

TeSys D

 
product or component type

Contactor

 
device short name

LC1D

 
contactor application

Resistive load
Motor control

 
utilisation category

AC-3
AC-4
AC-1

 
poles description

3P

 
power pole contact composition

3 NO

 
[Ue] rated operational voltage

Power circuit: <= 690 V AC 25...400 Hz
Power circuit: <= 300 V DC

 
[Ie] rated operational current

25 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
40 A (at <60 °C) at <= 440 V AC AC-1 for power circuit

 
motor power kW

5.5 kW at 220...230 V AC 50/60 Hz (AC-3)
11 kW at 380...400 V AC 50/60 Hz (AC-3)
11 kW at 415...440 V AC 50/60 Hz (AC-3)
15 kW at 500 V AC 50/60 Hz (AC-3)
15 kW at 660...690 V AC 50/60 Hz (AC-3)
5.5 kW at 400 V AC 50/60 Hz (AC-4)

 
motor power HP (UL / CSA)

3 hp at 230/240 V AC 50/60 Hz for 1 phase motors
2 hp at 115 V AC 50/60 Hz for 1 phase motors
7.5 hp at 230/240 V AC 50/60 Hz for 3 phases motors
15 hp at 460/480 V AC 50/60 Hz for 3 phases motors
20 hp at 575/600 V AC 50/60 Hz for 3 phases motors
7.5 hp at 200/208 V AC 50/60 Hz for 3 phases motors

 
control circuit type

AC at 50/60 Hz

 
[Uc] control circuit voltage

110 V AC 50/60 Hz

 
auxiliary contact composition

1 NO + 1 NC

 
[Uimp] rated impulse withstand voltage

6 kV conforming to IEC 60947

 
overvoltage category

III

 
[Ith] conventional free air thermal current

10 A (at 60 °C) for signalling circuit
40 A (at 60 °C) for power circuit

 
Irms rated making capacity

140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
450 A at 440 V for power circuit conforming to IEC 60947

 
rated breaking capacity

450 A at 440 V for power circuit conforming to IEC 60947

 
[Icw] rated short-time withstand current

240 A 40 °C - 10 s for power circuit
380 A 40 °C - 1 s for power circuit
50 A 40 °C - 10 min for power circuit
120 A 40 °C - 1 min for power circuit
100 A - 1 s for signalling circuit
120 A - 500 ms for signalling circuit
140 A - 100 ms for signalling circuit