top of page

LC2D12F7 Power Contactor is a TeSys Deca reversing contactor, 3 poles (3NO), for motor control applications up to 12A/690V AC-3 (5.5kW@400V). Rated 12A AC-3 5.5kW@400V, it includes a 110V 50/60Hz AC coil, 2NO+2NC aux contacts, a mechanical interlock.

It provides 110V 50/60Hz AC coils, 2NO+2NC built-in auxiliary contacts (NC mirror certified), connection by screw clamp terminals.

For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (90mm width), DIN-rail mounting or screw fixing.

With pre-wired reversing power connections, mechanical interlock (without electrical interlocking). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).

Assembled with mechanical interlock and pre-wired reversing circuit. Clear separation between power and control circuits, easy front access to coil and auxiliary contacts connections.

Equipped with a 110V AC coil that can be supplied at 50Hz or 60Hz. Provides 4 built-in auxiliary contacts 2NO + 2NC, NC contacts are mirror certified suitable to be included in the control of safety systems.

High electrical durability, guaranteed for 2 million cycles at 12A AC-3 440V, for demanding motor switching applications.

Robust design with high making and breaking capacities up to 20 In. Connection by screw clamp terminals.

 

Main
RangeTeSys
TeSys Deca
Product nameTeSys D
TeSys Deca
Product or Component TypeReversing contactor
Device short nameLC2D
Contactor applicationResistive load
Motor control
Utilisation categoryAC-3
AC-1
AC-3e
Device presentationPreassembled with reversing power busbar
Poles description3P
power pole contact composition3 NO
[Ue] rated operational voltagePower circuit <= 690 V AC 25...400 Hz
Power circuit <= 300 V DC
[Ie] rated operational current25 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit
12 A (at <140 °F (60 °C)) at <= 440 V AC AC-3 for power circuit
12 A (at <140 °F (60 °C)) at <= 440 V AC AC-3e for power circuit
Motor power kW3 kW at 220...230 V AC 50 Hz
5.5 kW at 380...400 V AC 50 Hz
5.5 kW at 415 V AC 50 Hz
5.5 kW at 440 V AC 50 Hz
7.5 kW at 500 V AC 50 Hz
7.5 kW at 660...690 V AC 50 Hz
motor power HP (UL / CSA)1 hp at 115 V AC 60 Hz for 1 phase motors
2 hp at 230/240 V AC 60 Hz for 1 phase motors
3 hp at 200/208 V AC 60 Hz for 3 phase motors
3 hp at 230/240 V AC 60 Hz for 3 phase motors
7.5 hp at 460/480 V AC 60 Hz for 3 phase motors
10 hp at 575/600 V AC 60 Hz for 3 phase motors
Control circuit typeAC 50/60 Hz
[Uc] control circuit voltage110 V AC 50/60 Hz
Auxiliary contact composition1 NO + 1 NC
[Uimp] rated impulse withstand voltage6 kV IEC 60947
Overvoltage categoryIII
[Ith] conventional free air thermal current10 A (at 140 °F (60 °C)) for signalling circuit
25 A (at 140 °F (60 °C)) for power circuit
Irms rated making capacity250 A at 440 V for power circuit conforming to IEC 60947
140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
Rated breaking capacity250 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current30 A 104 °F (40 °C) - 10 min for power circuit
61 A 104 °F (40 °C) - 1 min for power circuit
105 A 104 °F (40 °C) - 10 s for power circuit
210 A 104 °F (40 °C) - 1 s for power circuit
100 A - 1 s for signalling circuit
120 A - 500 ms for signalling circuit
140 A - 100 ms for signalling circuit
Associated fuse rating10 A gG for signalling circuit conforming to IEC 60947-5-1
40 A gG at <= 690 V coordination type 1 for power circuit
25 A gG at <= 690 V coordination type 2 for power circuit
Average impedance2.5 mOhm - Ith 25 A 50 Hz for power circuit
[Ui] rated insulation voltagePower circuit 690 V IEC 60947-4-1
Power circuit 600 V CSA
Power circuit 600 V UL
Signalling circuit 690 V IEC 60947-1
Signalling circuit 600 V CSA
Signalling circuit 600 V UL
Electrical durability2 Mcycles 12 A AC-3 <= 440 V
0.8 Mcycles 25 A AC-1 <= 440 V
2 Mcycles 12 A AC-3e <= 440 V
Power dissipation per pole1.56 W AC-1
0.36 W AC-3
0.36 W AC-3e
Front coverWith
Interlocking typeMechanical
Mounting SupportRail
Plate
StandardsCSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
IEC 60335-1
Product CertificationsDNV
CSA
CCC
UL
GL
LROS (Lloyds register of shipping)
BV
RINA
GOST
UKCA
  

LC2D12F7 Power Contactor

SKU: LC2D
₹900.00Price
Quantity