TeSys Deca, LRD08 thermal overload relay, 2.5 to 4 A, class 10A.
TeSys LRD overload relays are designed to be used with TeSys D contactors to make a motor starter. This overload relay can be used with 9 amp through 38 amp TeSys D contactors. These differential thermal overload relays detect over currents in the lines to the motor. When an overcurrent is detected the overload relay working with the contactor will disconnect the power to the motor. This will minimize the damage to the motor windings. This overload relay has an adjustable trip current rating of 2.5 to 4.0 amperes.
Main | ||
range | TeSys | |
---|---|---|
product name | TeSys LRD | |
product or component type | Differential thermal overload relay | |
device short name | LRD | |
relay application | Motor protection | |
product compatibility | LC1D12 | |
network type | AC | |
thermal overload class | Class 10A conforming to IEC 60947-4-1 | |
thermal protection adjustment range | 2.5…4 A | |
[Ui] rated insulation voltage | Power circuit: 600 V conforming to CSA |
Complementary | ||
network frequency | 0...400 Hz | |
---|---|---|
mounting support | Plate, with specific accessories | |
tripping threshold | 1.14 +/- 0.06 Ir conforming to IEC 60947-4-1 | |
auxiliary contact composition | 1 NO + 1 NC | |
[Ith] conventional free air thermal current | 5 A for signalling circuit | |
permissible current | 3 A at 120 V AC-15 for signalling circuit | |
[Ue] rated operational voltage | 690 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1 | |
associated fuse rating | 4 A gG for signalling circuit | |
[Uimp] rated impulse withstand voltage | 6 kV | |
phase failure sensitivity | Tripping current 130 % of Ir on two phase, the last one at 0 | |
control type | Red push-button: stop | |
temperature compensation | -20…60 °C | |
connections - terminals | Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² flexible without cable end | |
tightening torque | Control circuit: 1.7 N.m - on screw clamp terminals | |
height | 66 mm | |
width | 45 mm | |
depth | 70 mm | |
net weight | 0.124 kg |
Environment | ||
protective treatment | TH conforming to IEC 60068 | |
---|---|---|
IP degree of protection | IP20 conforming to IEC 60529 | |
ambient air temperature for operation | -20…60 °C without derating conforming to IEC 60947-4-1 | |
ambient air temperature for storage | -60…70 °C | |
flame retardance | V1 conforming to UL 94 | |
mechanical robustness | Vibrations: 6 Gn conforming to IEC 60068-2-6 | |
dielectric strength | 1.89 kV at 50 Hz conforming to IEC 60947-1 | |
standards | EN/IEC 60947-4-1 |