TeSys LRD14 thermal overload relay, 10A/690V, thermal setting range 7-10A, tripping class 10A, for protection of 3-phase motors 4kW@400V. Differential device with phase failure and load unbalance detection. It provides a thermal adjustement dial, a manual-automatic reset selector, a test selector for simulation of a tripping, reset and stop buttons, a flag indicator and 2 auxiliary contacts 1NO+1NC for fault signalling. Settings are protected by a transparent cover lockable by sealing.
Main | ||
range | TeSys | |
---|---|---|
product name | TeSys LRD | |
product or component type | Differential thermal overload relay | |
device short name | LRD | |
relay application | Motor protection | |
product compatibility | LC1D09 | |
network type | AC | |
thermal overload class | Class 10A conforming to IEC 60947-4-1 | |
thermal protection adjustment range | 7…10 A | |
[Ui] rated insulation voltage | Power circuit: 600 V conforming to CSA |
Complementary | ||
network frequency | 0...400 Hz | |
---|---|---|
mounting support | Plate, with specific accessories | |
tripping threshold | 1.14 +/- 0.06 Ir conforming to IEC 60947-4-1 | |
auxiliary contact composition | 1 NO + 1 NC | |
[Ith] conventional free air thermal current | 5 A for signalling circuit | |
permissible current | 3 A at 120 V AC-15 for signalling circuit | |
[Ue] rated operational voltage | 690 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1 | |
associated fuse rating | 4 A gG for signalling circuit | |
[Uimp] rated impulse withstand voltage | 6 kV | |
phase failure sensitivity | Tripping current 130 % of Ir on two phase, the last one at 0 | |
control type | Red push-button: stop | |
temperature compensation | -20…60 °C | |
connections - terminals | Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² flexible without cable end | |
tightening torque | Control circuit: 1.7 N.m - on screw clamp terminals | |
height | 66 mm | |
width | 45 mm | |
depth | 70 mm | |
net weight | 0.124 kg |
Environment | ||
protective treatment | TH conforming to IEC 60068 | |
---|---|---|
IP degree of protection | IP20 conforming to IEC 60529 | |
ambient air temperature for operation | -20…60 °C without derating conforming to IEC 60947-4-1 | |
ambient air temperature for storage | -60…70 °C | |
flame retardance | V1 conforming to UL 94 | |
mechanical robustness | Vibrations: 6 Gn conforming to IEC 60068-2-6 | |
dielectric strength | 1.89 kV at 50 Hz conforming to IEC 60947-1 | |
standards | EN/IEC 60947-4-1 |