top of page

 

TeSys LRD14 thermal overload relay, 10A/690V, thermal setting range 7-10A, tripping class 10A, for protection of 3-phase motors 4kW@400V. Differential device with phase failure and load unbalance detection. It provides a thermal adjustement dial, a manual-automatic reset selector, a test selector for simulation of a tripping, reset and stop buttons, a flag indicator and 2 auxiliary contacts 1NO+1NC for fault signalling. Settings are protected by a transparent cover lockable by sealing. 

 

Main
range

TeSys

 
product name

TeSys LRD

 
product or component type

Differential thermal overload relay

 
device short name

LRD

 
relay application

Motor protection

 
product compatibility

LC1D09
LC1D12
LC1D38
LC1D32
LC1D25
LC1D18

 
network type

AC
DC

 
thermal overload class

Class 10A conforming to IEC 60947-4-1

 
thermal protection adjustment range

7…10 A

 
[Ui] rated insulation voltage

Power circuit: 600 V conforming to CSA
Power circuit: 600 V conforming to UL
Power circuit: 690 V conforming to IEC 60947-4-1

 
Complementary
network frequency

0...400 Hz

 
mounting support

Plate, with specific accessories
Rail, with specific accessories
Under contactor

 
tripping threshold

1.14 +/- 0.06 Ir conforming to IEC 60947-4-1

 
auxiliary contact composition

1 NO + 1 NC

 
[Ith] conventional free air thermal current

5 A for signalling circuit

 
permissible current

3 A at 120 V AC-15 for signalling circuit
0.22 A at 125 V DC-13 for signalling circuit

 
[Ue] rated operational voltage

690 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1

 
associated fuse rating

4 A gG for signalling circuit
4 A BS for signalling circuit

 
[Uimp] rated impulse withstand voltage

6 kV

 
phase failure sensitivity

Tripping current 130 % of Ir on two phase, the last one at 0

 
control type

Red push-button: stop
Blue push-button: reset

 
temperature compensation

-20…60 °C

 
connections - terminals

Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² solid without cable end
Power circuit: screw clamp terminals 1 cable(s) 1.5…10 mm² flexible without cable end
Power circuit: screw clamp terminals 1 cable(s) 1…4 mm² flexible with cable end
Power circuit: screw clamp terminals 1 cable(s) 1…6 mm² solid without cable end

 
tightening torque

Control circuit: 1.7 N.m - on screw clamp terminals
Power circuit: 1.7 N.m - on screw clamp terminals

 
height

66 mm

 
width

45 mm

 
depth

70 mm

 
net weight

0.124 kg

 
Environment
protective treatment

TH conforming to IEC 60068

 
IP degree of protection

IP20 conforming to IEC 60529

 
ambient air temperature for operation

-20…60 °C without derating conforming to IEC 60947-4-1

 
ambient air temperature for storage

-60…70 °C

 
flame retardance

V1 conforming to UL 94

 
mechanical robustness

Vibrations: 6 Gn conforming to IEC 60068-2-6
Shocks: 15 Gn for 11 ms conforming to IEC 60068-2-7

 
dielectric strength

1.89 kV at 50 Hz conforming to IEC 60947-1

 
standards

EN/IEC 60947-4-1
EN/IEC 60947-5-1
UL 60947-4-1
UL 60947-5-1
CSA C22.2 No 60947-4-1
CSA C22.2 No 60947-5-1
GB/T 14048.4
GB/T 14048.5
EN 50495

LRD14 Thermal Overload Relay

SKU: LRD
₹1,295.00Price
Quantity